ML
    • Recent
    • Categories
    • Tags
    • Popular
    • Users
    • Groups
    • Register
    • Login

    EATON AMA

    IT Discussion
    eaton ama
    25
    208
    119.2k
    Loading More Posts
    • Oldest to Newest
    • Newest to Oldest
    • Most Votes
    Reply
    • Reply as topic
    Log in to reply
    This topic has been deleted. Only users with topic management privileges can see it.
    • coliverC
      coliver @windso
      last edited by

      @windso said:

      @coliver

      Two easy ways, one hard way.

      Easy

      1. Add all your IT load wattages together. Done 😉

      2. For 120V loads, take your server currents and multiply them all by 120V. If you have three phases, the process is the same: take all the currents, add together, multiply by 120V. Done!

      3. For 208V loads, avoid the physics lessons. Take the current on each "segment" and multiply by 208V * SQRT(3). Done!

      For those math nerds out there SQRT of three is based off of 120deg phase angle from your unit circle. OK. There are great resources out there on three phase power, but don't make it too complicated. The above equations can get you there.

      Wow... that is the simplest I've come across, we are running 208v. Thanks.

      1 Reply Last reply Reply Quote 1
      • dafyreD
        dafyre @windso
        last edited by

        @windso said:

        1. Add all your IT load wattages together. Done 😉

        Wattage of the Power Supplies, right?

        1. For 120V loads, take your server currents and multiply them all by 120V. If you have three phases, the process is the same: take all the currents, add together, multiply by 120V. Done!

        What do you mean by server currents?

        art_of_shredA windsoW 2 Replies Last reply Reply Quote 0
        • art_of_shredA
          art_of_shred Banned @dafyre
          last edited by

          @dafyre said:

          @windso said:

          1. Add all your IT load wattages together. Done 😉

          Wattage of the Power Supplies, right?

          1. For 120V loads, take your server currents and multiply them all by 120V. If you have three phases, the process is the same: take all the currents, add together, multiply by 120V. Done!

          What do you mean by server currents?

          Current is amps. My question about the wattage is do you go by the labeled wattage of the power supply, or do you need to calculate the actual operating load?

          JColeKenJ 1 Reply Last reply Reply Quote 1
          • scottalanmillerS
            scottalanmiller
            last edited by

            Server Current is the force of the flowing servers in the computational stream.

            art_of_shredA dafyreD 2 Replies Last reply Reply Quote 0
            • windsoW
              windso Vendor @dafyre
              last edited by

              @dafyre , good point, I edit the wording. See above. Really I mean current on each phase. Poorly worded. Sorry!

              1 Reply Last reply Reply Quote 1
              • art_of_shredA
                art_of_shred Banned @scottalanmiller
                last edited by

                @scottalanmiller said:

                Server Current is the force of the flowing servers in the computational stream.

                Don't try to answer electrical questions with IT answers. lol

                1 Reply Last reply Reply Quote 3
                • dafyreD
                  dafyre @scottalanmiller
                  last edited by

                  @scottalanmiller ❓ 💥 ❓ -- Mind = Blown

                  1 Reply Last reply Reply Quote 2
                  • JColeKenJ
                    JColeKen Vendor @dafyre
                    last edited by

                    @dafyre Cha-ching!

                    1 Reply Last reply Reply Quote 0
                    • JColeKenJ
                      JColeKen Vendor @art_of_shred
                      last edited by

                      @art_of_shred Actual operating load is the most practical.

                      coliverC art_of_shredA 2 Replies Last reply Reply Quote 0
                      • coliverC
                        coliver @JColeKen
                        last edited by

                        @JColeKen said:

                        @art_of_shred Actual operating load is the most practical.

                        How would you measure this in an environment without power monitoring? Or is it basically a guess at that point?

                        art_of_shredA 1 Reply Last reply Reply Quote 0
                        • art_of_shredA
                          art_of_shred Banned @JColeKen
                          last edited by

                          @JColeKen said:

                          @art_of_shred Actual operating load is the most practical.

                          Is there a simple percentage to use there as a ballpark figure?

                          JColeKenJ 1 Reply Last reply Reply Quote 0
                          • art_of_shredA
                            art_of_shred Banned @coliver
                            last edited by

                            @coliver said:

                            @JColeKen said:

                            @art_of_shred Actual operating load is the most practical.

                            How would you measure this in an environment without power monitoring? Or is it basically a guess at that point?

                            An ammeter works great if you have one and want real numbers.

                            scottalanmillerS windsoW 2 Replies Last reply Reply Quote 1
                            • JColeKenJ
                              JColeKen Vendor @art_of_shred
                              last edited by

                              @art_of_shred 70-80% is a safe bet. Sometimes it is lower, but that is typically what I default to when sizing.

                              1 Reply Last reply Reply Quote 2
                              • scottalanmillerS
                                scottalanmiller @art_of_shred
                                last edited by

                                @art_of_shred said:

                                @coliver said:

                                @JColeKen said:

                                @art_of_shred Actual operating load is the most practical.

                                How would you measure this in an environment without power monitoring? Or is it basically a guess at that point?

                                An ammeter works great if you have one and want real numbers.

                                Even in the afternoon or do you have to switch to a PMmeter?

                                JColeKenJ art_of_shredA 2 Replies Last reply Reply Quote 1
                                • windsoW
                                  windso Vendor @art_of_shred
                                  last edited by windso

                                  @art_of_shred @coliver

                                  Yes! These can be somewhat inexpensive. We usually see IT equipment running at 60% or less of nameplate rating. The challenge we have when sizing a UPS or PDU, and you will have too, is that generic rules always bite you at some point. If you are the exception, you risk taking down everything.

                                  Keep in mind that sizing a UPS or PDU at less than 80% or 100% utilization is a good thing. UPSs and PDUs are like the breakers feeding your Christmas tree lights - Once you add too much, the lights go off!

                                  art_of_shredA 1 Reply Last reply Reply Quote 3
                                  • JColeKenJ
                                    JColeKen Vendor @scottalanmiller
                                    last edited by

                                    @scottalanmiller Lolz

                                    1 Reply Last reply Reply Quote 1
                                    • art_of_shredA
                                      art_of_shred Banned @scottalanmiller
                                      last edited by

                                      @scottalanmiller said:

                                      @art_of_shred said:

                                      @coliver said:

                                      @JColeKen said:

                                      @art_of_shred Actual operating load is the most practical.

                                      How would you measure this in an environment without power monitoring? Or is it basically a guess at that point?

                                      An ammeter works great if you have one and want real numbers.

                                      Even in the afternoon or do you have to switch to a PMmeter?

                                      Once again sporting your prowess in all things electrical. I defer to your expertise...

                                      1 Reply Last reply Reply Quote 1
                                      • NicN
                                        Nic
                                        last edited by

                                        Couple of ones that might be more home oriented than business:

                                        1. Do you have any plans to get into the home battery market, like Tesla? (or are you already) These are the backup batteries that you can charge from solar and then power your home from (or use as a backup for if the power is out).
                                        2. What would you recommend in the prosumer market for IT pros or technically minded folks to use at home?
                                        windsoW 1 Reply Last reply Reply Quote 4
                                        • art_of_shredA
                                          art_of_shred Banned @windso
                                          last edited by

                                          @windso said:

                                          @art_of_shred @coliver

                                          Yes! These can be somewhat inexpensive. We usually see loads running at 60% or less of nameplate rating. The challenge we have, and you will have too, is that generic rules always bite you at some point. If you are the exception, you risk taking down everything.

                                          Keep in mind that sizing a circuit at less than 80% or 100% is a good thing. You never want to completely oversize, but UPSs and PDUs are like the breakers feeding your Christmas tree lights - Once you add too much, the lights go off!

                                          Just to clarify, I thought that was worded a little confusingly. You never want your load to equal or surpass your protection. Ideally, your expected amp load should only be about 80% of your protection's full capacity. Otherwise, you can exceed its ability to protect and either diminish its performance or nullify the protection altogether.

                                          windsoW 1 Reply Last reply Reply Quote 2
                                          • art_of_shredA
                                            art_of_shred Banned
                                            last edited by

                                            That didn't sound good when I read it, so keep your mind out of the gutter.

                                            scottalanmillerS 1 Reply Last reply Reply Quote 0
                                            • 1
                                            • 2
                                            • 5
                                            • 6
                                            • 7
                                            • 8
                                            • 9
                                            • 10
                                            • 11
                                            • 7 / 11
                                            • First post
                                              Last post