    • J
      Jason Banned @MattSpeller
      last edited by Jason

      @MattSpeller said:

      There will absolutely be one between the UPS and the telephone pole - for a proper test I highly recommend flipping it. Sometimes you find little surprises that would completely screw you. Also you learn how long your UPS actually lasts and you can test your graceful shutdown setup.

      We don't touch that kind of stuff. Yes I know there is a three phase main breaker for it somewhere but we don't mess with the UPS, Breaks or anything. It's not IT. it all gets tested by Facilities. IT would get fired for messing with electrical stuff.

      1 Reply Last reply Reply Quote 0
      • J
        Jason Banned @MattSpeller
        last edited by

        @MattSpeller said:

        Also you learn how long your UPS actually lasts and you can test your graceful shutdown setup.

        We don't worry about the Graceful shutdowns too much. We have multiple three phase feeds from two different utilities. two Generators and two UPS systems.

        We can run forever (as long as there is natural gas lines still working) on generators. and up to 48hrs on UPS power.

        1 Reply Last reply Reply Quote 0
        • BRRABillB
          BRRABill
          last edited by

          Was there ever a comment/decision on whether to run both power supplies into 1 UPS, 2 UPSes, or 1 UPS and a regular surge protector?

          In my location there is just the one circuit. I have no other options.

          brianlittlejohnB scottalanmillerS 2 Replies Last reply Reply Quote 0
          • brianlittlejohnB
            brianlittlejohn @BRRABill
            last edited by

            @BRRABill ideally you split the power supplies across 2 UPS so a ups failure doesn't take your stuff out.

            1 Reply Last reply Reply Quote 1
            • scottalanmillerS
              scottalanmiller @BRRABill
              last edited by

              @BRRABill said:

              Was there ever a comment/decision on whether to run both power supplies into 1 UPS, 2 UPSes, or 1 UPS and a regular surge protector?

              In my location there is just the one circuit. I have no other options.

              Yes, there was never any question or grey area there. Each PSU goes to an separate UPS.

              1 Reply Last reply Reply Quote 0
              • BRRABillB
                BRRABill
                last edited by

                Another question...

                I'm assuming it is going to be based on run time, but it seems like UPS manufacturers always seem to want to sell me something that seems to be 10x more than I need.

                For a 495W power supply, what kind of UPS would you be thinking about?

                Also, would you go "server grade" or just go with a nice desktop unit.

                I'm talking specifically about my (2) 495W power supple DELL T320, but I'm just asking in general.

                MattSpellerM 1 Reply Last reply Reply Quote 0
                • brianlittlejohnB
                  brianlittlejohn
                  last edited by

                  Do you have iDrac enterprise on that server? If so, it will show you what your actual wattage is being pulled on your powersupply. That may help you better find a UPS to fit your needs.

                  On one of my servers I've only peaked to 260W of my dual 750W Power Supplies.

                  1 Reply Last reply Reply Quote 0
                  • BRRABillB
                    BRRABill
                    last edited by

                    No, but I do have a Kill-A-Watt.

                    1 Reply Last reply Reply Quote 0
                    • Reid CooperR
                      Reid Cooper
                      last edited by

                      I would consider upgrading to iDrac Enterprise for any server. Especially when you have them a single servers and at client sites.

                      1 Reply Last reply Reply Quote 0
                      • MattSpellerM
                        MattSpeller @BRRABill
                        last edited by MattSpeller

                        @BRRABill said:

                        I'm assuming it is going to be based on run time, but it seems like UPS manufacturers always seem to want to sell me something that seems to be 10x more than I need.

                        That's their job 😛

                        For a 495W power supply, what kind of UPS would you be thinking about?

                        Minimum 1000va for the cost / runtime / quality points to all meet up IMHO. YMMV. You need to do your homework with manglement and make sure you have enough runtime to satisfy the business needs, then add some for growth and battery life dropping off over time. Don't forget to budget for battery replacements every 3 years.

                        Also, would you go "server grade" or just go with a nice desktop unit.

                        I'd go with what you can afford that meets your run time requirements (plus ~20% for battery performance drop off) from a reputable manufacturer!

                        Keep in mind that a good quality UPS with nice features is worth it. Having a small software app and a USB or network connection so the UPS can shutdown your server is a minimum requirement for me. Highly recommend.

                        I'm talking specifically about my (2) 495W power supple DELL T320, but I'm just asking in general.

                        I'd suggest the below but there are lots of them out there.
                        http://powerquality.eaton.com/Products-services/Backup-Power-UPS/5S.aspx?cx=3

                        BRRABillB 1 Reply Last reply Reply Quote 1
                        • J
                          Jason Banned
                          last edited by

                          Just get a 1500va Tripplite and you should be good. The SmartPro 1050 should be around $400.

                          1 Reply Last reply Reply Quote 0
                          • MattSpellerM
                            MattSpeller
                            last edited by MattSpeller

                            UPS have a lot of traps that really suck if you get wrong.

                            Volt Amps / VA = run time.

                            Watts = how much it can run. Fun fact: this is a number not to exceed and I highly suggest getting one rated generously (25% or better) above your requirements.

                            Why is this a trap you ask?

                            Most UPS are rated in VA because the number is bigger. The actual wattage the unit can supply is generally half this, but it varies A LOT so check!

                            Other things to think about:

                            What voltage does the UPS output? What voltage do your servers need? Don't expect 110v unless you've checked it.

                            What kind of plug connects the UPS to the city's power? This is more of a concern with the larger units.

                            How much wattage and run time do you really need? Power supply rated for 500w in a server is probably not pulling half that. Couple ways you can verify this, but make sure you do.

                            Dual power supplies? They don't add together! Dual 1000w power supplies will draw a maximum of 1000w. But you already knew that because you read the question above and checked..... right? 🙂

                            How much run time does the business require? Usually it's also answerable in "how long does it take to shut down all the servers?"

                            Any VOIP/PoE phones require keeping the network running for 911?

                            BRRABillB 1 Reply Last reply Reply Quote 0
                            • BRRABillB
                              BRRABill @MattSpeller
                              last edited by

                              @MattSpeller said:

                              I'd suggest the below but there are lots of them out there.
                              http://powerquality.eaton.com/Products-services/Backup-Power-UPS/5S.aspx?cx=3

                              That's kind of what I was thinking.

                              I spoke to Eaton, and they recommended the 5P1500.

                              But trying to go the "cheap" route has been getting me in trouble here. 🙂 I just want to know VA/WATTAGE wise if they are the same, why go for the servver-grade model?

                              The "S" model you recommnded is less than half the price.

                              1 Reply Last reply Reply Quote 0
                              • BRRABillB
                                BRRABill @MattSpeller
                                last edited by

                                @MattSpeller said:

                                UPS have a lot of traps that really suck if you get wrong.

                                Is topology one of those traps?

                                1 Reply Last reply Reply Quote 0
                                • BRRABillB
                                  BRRABill
                                  last edited by

                                  I mean sine wave topology, which probably isn't topology.

                                  MattSpellerM 1 Reply Last reply Reply Quote 0
                                  • MattSpellerM
                                    MattSpeller @BRRABill
                                    last edited by

                                    @BRRABill Yup, sure is. To be honest, if you're just powering computers it makes very little difference. You could actually feed the computers pure DC (no AC sine wave) and they'd work just fine. Where you get into trouble is stuff like electric motors, air conditioners, anything that plugs straight into the wall without a power supply (wall wart).

                                    1 Reply Last reply Reply Quote 0
                                    • scottalanmillerS
                                      scottalanmiller
                                      last edited by

                                      You can buy DC powered servers. They create less heat and suck less overall power.

                                      MattSpellerM 1 Reply Last reply Reply Quote 0
                                      • MattSpellerM
                                        MattSpeller @scottalanmiller
                                        last edited by

                                        @scottalanmiller said:

                                        You can buy DC powered servers. They create less heat and suck less overall power.

                                        whoa, TIL

                                        1 Reply Last reply Reply Quote 1
                                        • BRRABillB
                                          BRRABill
                                          last edited by

                                          What do you think about the "S" line versus the "P" line.

                                          Big cost savings.

                                          JaredBuschJ 1 Reply Last reply Reply Quote 0
                                          • JaredBuschJ
                                            JaredBusch @BRRABill
                                            last edited by

                                            @BRRABill said:

                                            What do you think about the "S" line versus the "P" line.

                                            Big cost savings.

                                            The P line has 2 distinct output groups. The S does not. Basically a feature you may or may not desire or need. Personally, I would skip it and go with the S as long as it works with their software. The software monitoring account for a lot IMO.

                                            img

                                            BRRABillB 1 Reply Last reply Reply Quote 1